products

The Cooling Water System Of The Oled Plant Saves $437,500 And 900,000 Tons Of Tap Water Every Year. Using Qimen Cooling Water Treatment Solution

Publish Time: 2025-05-12

Target


Use reclaimed water as cooling water system replenishment


Reduce tap water consumption


Eliminate scaling problems caused by aluminum salts carried in the backwash water of multimedia filters.


Reduce operating costs of clarification and cooling towers

 

Plan


Upgrade to Qimen cooling water treatment solution to eliminate the risk of carbonate deposition


Reclaimed water quality

Controlling water quality

Calcium hardness is measured in CaCO3

130 ppm

500 ppm

Conductivity

335us/cm

1500us/cm

pH

8.0

8.0-9.0

Aluminum salts

1.3 ppm

5ppm

MAlkalinity

100

500

Concentration multiple

 

4


Result


The system has been running continuously for 7 years without scaling.


Save 900,000 tons of tap water.


Save $437,5K/year

×

Contact Us